FTPI RP 2007-2 Field Test Protocol for Testing the Annular Space Of Installed Underground Fiberglass Double and Triple-Wall Tanks With Dry Annular Space
Click here for print version
Introduction: This field test procedure is designed to test
the integrity of the dry annular space of double or triple wall
underground fiberglass storage tanks. The test procedure
draws a vacuum on the annular space and monitors for vacuum decay
over a prescribed period of time. The vacuum test time depends on
the volume of the annular space and the installation site
conditions. The underground fiberglass tank may contain any level of liquid (e. g. product
or water) and liquid may be removed or added at any time during the
annular space test. However, product deliveries should be avoided if
possible. If a delivery occurs during the test and the vacuum
experiences a significant change, the test should be restarted.
Test Time: The procedures require a vacuum to be drawn on
each tank annular space and held for a period of time. The vacuum
should be expected to decay over time. However, there is a time
period that has been established by laboratory tightness testing to
recognize an acceptable change in the vacuum level and this will
vary based on the tank annular space volume, the type of fluid in the tank and
the backfill conditions. The test procedures require an initial vacuum of 10” Hg
during the initial hold time and a maximum vacuum loss of 2” Hg. If the vacuum
loss exceeds 2” Hg during the hold time, the test is repeated.
The hold times will be different based on the volume of the annular space - the
larger the space the longer the hold time. The annular space volume is a
function of the tank volume and the manufacturer’s method of creating the
annular space.
If a leak is present and the leak is a non-volatile fluid like water or diesel
fuel, the given testing times will apply but it is necessary to confirm after
the vacuum test that the annular space did not accumulate any liquid during the
test. If the leak is air or a volatile fluid like gasoline, the leak will be
evident based on the vacuum test results.
Be sure to follow all federal, state, local
rules and OSHA safety procedures.
- Obtain owner verification that the primary
tank is currently sound and has not leaked in the past.
- If possible, confirm that there is no liquid
in the interstitial space with a hand or electronic sensor.
- Use a venturi-eductor type air mover only.
Do not use an electric or gasoline vacuum pump. Use of a vacuum pump could
result in a safety hazard if flammable liquids are present.
- If a leak of volatile fluid like gasoline is
present, the exhaust from the venturi may contain flammable vapors.
- Do not apply a vacuum to the primary tank.
Equipment Required
- A vacuum gauge with a range of 0-30” Hg with increments of 0.5” Hg or
smaller.
- A small air driven venturi capable of pulling 15” Hg when operated with
compressed air.
- A valve and an air hose.
- A vacuum regulator or automatic shut-off valve that will shut off at 12”
Hg
Pretest Procedure
- Check to make sure that the tank to be tested is a dry monitored tank. If
it is a wet monitored tank, it does not need to be tested with this
procedure. However, check the brine level – if it is within proper levels,
the tank meets the annular space integrity requirements. If the brine is
outside the specified requirements, contact the manufacturer.
- Determine if the interstitial space is a “tight wrap” design or an
earlier 1980’s vintage “110% containment” design with a larger volume
interstitial space. If the interstitial space is a “tight wrap” then the
test times will be shorter.
- Check the annular space for vapors or liquid. If the annular space is
free of vapors and liquid, proceed with the test.
- If vapors or liquid are found, investigate the source and determine
whether the tank is leaking. If the tank is found to be leaking, do not
continue beyond this step and contact the manufacturer.
- If you are unable to determine if the annular space is free of vapors and
liquid, proceed with the test.
- Identify the volume of the tank. The test time will vary with tank size.
Test Procedure
- Connect the vacuum gauge, valve and vacuum venturi to an annular space
fitting. The valve should be between the compressor and the fitting. The
gauge should be between the valve and the fitting so it will read when the
valve is closed. It is highly recommended to use an automatic vacuum
shut-off valve and set it at 12” Hg.
- Ensure all connections are airtight.
- Start the vacuum venturi and open the valve.
- When the vacuum level reaches 12” Hg, close the valve and stop the vacuum venturi (do not exceed 12” Hg vacuum).
- Wait until the vacuum level stabilizes at or above 10” Hg. Increase to
12” Hg again if necessary by repeating steps 3 and 4. Hold for 5 minutes or
longer at 10” Hg, with a vacuum decrease of less than 0.5” Hg. If a stable
vacuum cannot be maintained, a leak is indicated and the test should be
terminated.
- Record the vacuum level and the time.
- Hold the initial vacuum for the period of time shown in the following
tables based on tank size and type.
Hold times for “tight wrap” tanks:
|
Tank Capacity * |
Hold Time |
|
Up to 15,000 gallons |
1 Hour |
|
Over 15,000 and up to
24,000 gallons |
2 Hours |
|
Over 24,000 and up to
34,000 gallons |
3 Hours |
|
Over 34,000 and up to
44,000 gallons |
4 Hours |
|
Over 44,000 gallons and
up to 50,000 gallons |
5 Hours |
|
*This is the total tank capacity, including all compartments in a
multi-compartment tank. |
Hold times for “110% containment” tanks:
|
Tank Capacity * |
Hold Time |
|
Up to 2,000 gallons |
1 Hour |
|
Over 2,000 and up to
5,000 gallons |
2 Hours |
|
Over 5,000 and up to
9,000 gallons |
3 Hours |
|
Over 9,000 and up to
14,000 gallons |
4 Hours |
|
Over 14,000 and up to
19,000 gallons |
6 Hours |
|
Over 19,000 and up to
24,000 gallons |
8 Hours |
|
Over 24,000 and up to
29,000 gallons |
10 Hours |
|
Over 29,000 gallons and
up to 30,000 gallons |
12 Hours |
|
*This is the total tank capacity, including all compartments in a
multi-compartment tank. |
If the vacuum level is 8” Hg or higher at the end of the hold time, and
the annular space is dry, the tank has passed the test.
If the tank vacuum level is below 8” Hg after the specified time, go back
and repeat, starting at step 2.
If the tank fails to hold 8” Hg after three attempts, call the tank
manufacturer.
The presence of water or fuel in an annular space that was dry at the
beginning of the test will confirm that that a leak is present.
On triple wall tanks, follow steps 1 through 10 for each annular space.
IMPORTANT NOTICE
I. This field test protocol, published by the Fiberglass Tank and Pipe
Institute (“Institute”), addresses subjects of a general nature associated
with the testing of the annular space in installed fiberglass-reinforced
plastic double and triple-wall tanks with dry annular space as part of
underground storage tank (UST) system. Federal, State and local laws and
regulations governing the testing of such installations and UST systems
should be reviewed. Trained personnel should perform the types of work
covered by the field test protocol.
II. When the field test protocol is complete, one copy of the results should
be retained in the tester’s files, and one copy in the owner/operator’s
file.
III. The Institute is not undertaking to meet the duties of underground
storage tank system owners/operators, employers, manufacturers, or suppliers
to warn and properly train and equip their employees, and others exposed or
in contact with fiberglass tanks and materials, concerning their obligations
under Federal, State or local laws or regulations, as well as health and
safety risks and precautions.
IV. Information concerning safety and health risks and proper precautions
with respect to particular materials and conditions should be obtained from
the manufacturer or supplier of the material, or the applicable material
safety data sheet.
THE FIELD TEST PROTOCOL MAY BE USED BY ANYONE DESIRING TO DO SO. EVERY
EFFORT HAS BEEN MADE BY THE INSTITUTE TO ASSURE THE ACCURACY AND RELIABILITY
OF THE INFORMATION IT CONTAINS. HOWEVER, THE INSTITUTE MAKES NO
REPRESENTATION, WARRANTY, OR GUARANTEE IN CONNECTION WITH THIS FIELD TEST
PROTOCOL AND HEREBY EXPRESSLY DISCLAIMS ANY LIABILITY OR RESPONSIBILITY FOR
LOSS OR DAMAGE, INCLUDING PERSONAL INJURY OR PROPERTY OR OTHER DAMAGES OF
WHATEVER NATURE, RESULTING FROM ITS USE OR FOR THE VIOLATION OF ANY FEDERAL,
STATE, OR LOCAL LAW OR REGULATION WITH WHICH THIS CHECKLIST MAY CONFLICT.
V. If you have questions concerning the proper testing the annular space of
fiberglass double and triple-wall underground storage tanks, contact the
manufacturer. Institute testing protocol sponsors are listed below:
Cardinal Fibreglass
Industries 700 Hicks Street Brooklyn, N.Y. 11231 Phone: 718-625-4350 |
Containment Solutions, Inc.
5150 Jefferson Chemical Rd.
Conroe, Texas 77301-6834
Phone: 936-756-7731 |
Owens Corning Fiberglass
Corp. Fiberglass Tower Toledo, OH 43659 Phone: 936-273-4383 |
Xerxes Corporation
7901 Xerxes Ave. South
Minneapolis, MN 55431
Phone: 952-887-1890 |
VI. Comments and suggested revisions to this field test protocol are
invited. Contact:
Sullivan (Sully) D. Curran, Executive Director Fiberglass Tank & Pipe Institute
11150 S. Wilcrest Dr., Suite 101
Pub No. FTPI RP 2007-2
|